Quality Inspection for China Supplier Plate Heat Exchanger Core - Liquid Circulation Heat Exchangers – Holtop

Products Detail
Our firm sticks to the basic principle of "Quality is the life of your company, and status will be the soul of it" for industrial air handling system , air treatment , Wall Mounted , Never-ending improvement and striving for 0% deficiency are our two main quality policies. Should you need anything, don't hesitate to contact us.
Quality Inspection for China Supplier Plate Heat Exchanger Core - Liquid Circulation Heat Exchangers – Holtop Detail:

Liquid Circulation Heat Exchanger -Heat recovery core of AHU

Working Principle

Liquid circulation heat exchanger is liquid to air heat exchanger, heat exchangers usually installed in both fresh air (OA) side and exhaust air (EA) side, the pump between the two heat exchangers make the liquid circulate, then the heat in the liquid pre-heat or pre-cool the fresh air. Normally the liquid is water, but In winter, in order to decrease the freezing point, moderate ethylene glycol will be added into the water in reasonable percentage.

Features of Holtop Liquid Circulation Heat Exchanger

(1) Fresh air and exhaust air heat exchanged by separated liquid pipes, zero cross contamination. It suitable for heat recovery energy saving of air handling system of hospital, germfree lab and industries which discharge poisonous and harmful gas.

(2) Stable,reliable and long service life

(3) Flexible connection between fresh air and exhaust air exchangers, easy installation, which also is convenient for old AHU improvement.

(4) Heat exchangers are conventional, easy and low maintenance costs.

(5) Wide range of application, various connection methods like one to one, one to more, or many to many.

Specifications  

(1) Liquid circulation heat exchangers is sensible heat exchangers, efficiency is between 55% to 60%.

(2) Suggested rows number in 6 or 8, face velocity not over 2.8 m/s

(3) The choice of circulating pump can refer to the fresh air and exhaust air pressure drop and the water flows pressure drop.

(4) Air flow direction has significant effect on the heat recovery efficiency, influence rate up to 20%.

(5) Freezing point of the hybrid ethylene glycol and water should be 4-6 ℃ lower than the local minimum outdoor temperature of winter, percentage of hybrid can be referred to the following table.

Freezing point -1.4 - 1.3 -5.4 -7.8 -10.7 -14.1 -17.9 -22.3
Weight percentage (%) 5 10 15 20 25 30 35 40
Volume percentage (%) 4.4 8.9 13.6 18.1 22.9 27.7 32.6 37.5
  • Previous: Combine Air Handling Units AHU
  • Next: Heat Pipe Heat Exchangers

Product detail pictures:

Quality Inspection for China Supplier Plate Heat Exchanger Core -
 Liquid Circulation Heat Exchangers – Holtop detail pictures


Related Product Guide:

We have the most advanced production equipment, experienced and qualified engineers and workers, recognized quality control systems and a friendly professional sales team pre/after-sales support for Quality Inspection for China Supplier Plate Heat Exchanger Core - Liquid Circulation Heat Exchangers – Holtop , The product will supply to all over the world, such as: Miami , Curacao , Slovakia , Upon today, we have customers from all over the world, including USA, Russia, Spain, Italy, Singapore, Malaysia, Thailand, Poland, Iran and Iraq. The mission of our company is to provide the highest quality products with best price. We are looking forward to doing business with you.
  • This company has a lot of ready-made options to choose and also could custom new program according to our demand, which is very nice to meet our needs.
    5 Stars By Juliet from Iraq - 2017.09.30 16:36
    Although we are a small company, we are also respected. Reliable quality, sincere service and good credit, we are honored to be able to work with you!
    5 Stars By Ann from Burundi - 2017.11.01 17:04
    Write your message here and send it to us